Dust-Hog SUPRA-CONIC Owner's Manual Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
23
United Air Specialists, Inc.
Supra-Pulse FJH Series
Cartridge Dust Collector
Revised 02/02
MAGNEHELIC GAGE CONTROL WITH
SUPRA-CLEAN TIMERBOARD
When using a Magnehelic Gage with Supra-Clean
pulse timerboard, the timerboard is always set to
“Continuous Clean” pulse mode. If the filters are
operating at a higher or lower differential pressure than
desired, adjusting the pulse frequency (Pulse Delay)
can often modify the steady-state pressure differential.
The factory setting is 10-second intervals. Adjust the
“Pulse Delay” on the Supra-Clean timerboard and
monitor the pressure drop on the Magnehelic Gage. A
longer interval will raise the operating differential
pressure and a shorter interval will lower the operating
differential pressure. Allow sufficient time for the system
to stabilize after each adjustment before further
adjustment is made. Adjust unit the desired pressure
differential is reached.
PHOTOHELIC GAGE CONTROL WITH
SUPRA-CLEAN TIMERBOARD
When using a Photohelic Gage with Supra-Clean pulse
timerboard, the timerboard can set to “PS” pulse mode
(pulse cleaning activated by the Photohelic control) or
“Continuous Clean” pulse mode to override the
Photohelic Gage. With the Photohelic Gage control, the
desired pressure differential can be maintained by
adjusting the high and low setpoints on the gauge.
Adjust the upper setpoint to the desired differential
pressure setting plus 0.25" (factory recommended
setting is 3"). Adjust the lower setpoint to the desired
setting minus 0.25" (factory recommended setting is
2.5"). This allows a 0.5" “deadband” and the pulse
system will maintain the desired differential pressure
(factory recommended operating point is 2.75"). If the
differential pressure remains above the desired
operating point, the pulse frequency can be increased
(shorter “Pulse Delay”) as previously described. The
high and low needle setpoints on the Photohelic Gage
can be adjusted as the filters season and continuous
pulsing occurs. Adjust both needles upward in 0.5"
increments until pulsing stops. Continue adjustments,
when required, until the high setpoint reaches 6". No
further adjustments should be made above 6" w.g.
SUPRA-VIEW PULSE PANEL
When using the Supra-View panel, the pulsing controls
can be set to “PS” pulse mode (“On-Demand” cleaning
similar to Photohelic control) or “Continuous Clean”
pulse cleaning. The Supra-View comes standard with a
cartridge differential measurement/display, pulse time
sequence controls and a “Customer usable” high
cartridge pressure alarm contact all in one enclosed
assembly. The high, low and alarm setpoints are
adjusted by opening the enclosure door and adjusting
the appropriate selector switches for desired control.
Adjustments to the setpoints can only be done with the
door open. Refer to the Supra-View
Installation and
Operation Manual
for adjustment details, or look on the
inside of the Supra-View enclosure door for operating
instructions.
SUPRA-I.Q. DIAGNOSTIC PANEL
The Supra-I.Q. Diagnostics Panel can be set to operate
in Continuous Clean, Setpoint Clean (similar to
Photohelic control), or “Autotune” Clean mode. Autotune
mode is designed to conserve compressed air usage
while maintaining lowest possible cartridge differential
pressure. It allows the minimal amount of compressed
air usage while maximizing filter life. In Autotune mode,
the controller will automatically adjust the filter
differential pressure to obtain the most cost-effective
setting. Please refer to the Supra-I.Q.
Installation and
Operation Manual
for a complete listing of operating
parameters and adjustment instructions.
ALL CONTROL OPTIONS
As filter cartridges become loaded with dust, the
differential pressure across the filters will increase. This
will result in a loss of air volume. Should the dust
collection capture effectiveness be reduced, open the
flow control damper to return the system to the original
design air volume.
6. SERVICE
BEFORE SERVICING,
NOTE THE FOLLOWING:
1. Disconnect electrical power to the unit and
control panel.
2. Shut off and slowly bleed compressed air supply
from the manifold.
3. Collected dust may be hazardous. Consult proper
authorities for handling and disposal.
4. Collected dust may be a potential fire hazard.
Welding, grinding or operations involving open
flames should NOT be performed without fire
protection measures in place. Refer to Section
1 of this manual for additional precautions.
5. Wear appropriate protective clothing when servicing
the dust collector.
6. Disposal of collected dust must be according to state
and local environmental regulations.
Page view 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 39 40

Comments to this Manuals

No comments