United Air Specialists, Inc.
Supra-Pulse FJH Series
Cartridge Dust Collector
Revised 02/02
When multiple module solenoid valve enclosures with
heaters are installed, daisy chain the wiring so that each
heater will have 100/115/VAC, 50/60Hz at all times. Make
certain enough current is available to supply all heaters.
Example: If three solenoid valve enclosures are
supplied with cartridge heaters, make certain the
voltage supply can deliver 3 amps (1 amp per heater).
5. OPERATION
5.1 START UP
Inspect the installation area and make certain no tools,
parts, etc. have been left anywhere on or inside the FJH
unit. Check blower discharge to make certain it is free
from all debris.
Start motor/blower and check for proper rotation. A
rotation arrow is located on the blower housing. All top-
mount blower assemblies rotate in a clockwise rotation
as viewed from the driven end (motor end with motor
cooling fan). If the blower is rotating in the opposite
direction, disconnect the power to the motor starter. For
3-phase blowers, interchange any two power wires to
the motor at the load side of the motor starter contactor.
For single-phase power, refer to motor nameplate for
which two wires to interchange at motor junction box.
Engage starter disconnect, start blower and recheck
rotation.
NOTE: Proper blower rotation is required to move the
designed amount of air. A blower rotating in the
incorrect direction will only move about 40% of
design airflow.
NOTE: It is important that the air volume of the dust
collection system is at design conditions at
system start-up. There is a minimal pressure
differential across new cartridge filters. If the
volume control damper is not correctly
adjusted, the air volume will be above design
conditions for airflow and may affect the
cartridge filter life.
The air volume should be adjusted based on the
performance of the entire system. Air volume control
damper should be adjusted to the system design
conditions. Closing the volume damper decreases
system airflow. Opening the volume damper increases
system airflow.
On certain applications, it may be beneficial to “seed” or
pre-coat the original or replacement cartridge filters.
This process introduces a certain amount of coating
(usually crushed limestone, agricultural lime or other
specifically marketed pre-coat) in light concentration to
deposit a thin coating of material which acts as an aid to
filtration. This deposited dust cake keeps the dust
loading on the surface of the cartridge filter. This
process will increase filter life and efficiency while
allowing the cleaning system to work more effectively.
For filter seeding procedures, refer to Section 6.2.
Turn on the compressed air supply to the dust collector
air manifold reservoir. Adjust the pressure regulator until
the gauge reads 90-110PSIG (6.2-7.6BAR).
!
CAUTION
Shut off unit disconnect and lock out all electrical
power to the dust collector prior to performing
service work.
!
CAUTION
Prior to unit start-up, all installation set-up instructions
must be completed as specified by this manual,
Supra-Clean
Installation and Operation Manual
,
Supra-View
Installation and Operation Manual
, Supra-
I.Q.
Installation and Operation Manual
, as well as any
manuals supplied by other equipment manufacturers,
as they apply to your dust collector.
!
CAUTION
The blower assembly provided by United Air
Specialist, Inc. includes an outlet damper. If the blower
assembly was purchased separately, ensure a volume
control damper is included somewhere in the dust
collection system. Close the blower discharge damper
to 50% open position and tighten in place. If a volume
control damper is provided in another part of the dust
collection system, adjust second damper to the 50%
open position and tighten in place.
!
CAUTION
Verify dust collector system airflow is adjusted to
design conditions with new, clean filters using the
volume control dampers installed in the system.
Failure to properly adjust system airflow may affect
cartridge filter life.